    A Multistage Passive Islanding Detection Method for Synchronous-Based Distributed Generation

    Thumbnail
    View/ Open
    10 - A Multistage Passive Islanding Detection Method for Synchronous-Based Distributed Generation.pdf (1.304Mb)
    Date
    2021-03
    Author
    Sawas, Abdullah M.
    Woon, Wei Lee
    Pandi, V. Ravikumar
    Shaaban, Mostafa
    Zeineldin, H. H.
    Advisor(s)
    Unknown advisor
    Type
    Article
    Peer-Reviewed
    Postprint
    Metadata
    Show full item record
    Abstract
    A multistage approach to passive islanding detection is proposed that utilizes a decision tree (DT) like classification algorithm. The novelty of the proposed method is centered on the way in which features are passed to subsequent stages of the DT. Feature sets extracted using different sized time windows are passed to successive stages of the tree. This provides two important advantages: 1) cases that can be easily determined as either islanding or nonislanding events are flagged as soon as possible without waiting for the full feature set to become available; 2) because the algorithm allows for the use of different sized time windows, features are analyzed in time-scales that fit their natural patterns of temporal evolution. In this article, the proposed classifier is trained and tested using a database of feature vectors, obtained using PSCAD, which were designed to reflect a variety of commonly encountered events on an IEEE 34-bus distribution system. One of the key requirements for the proposed algorithm was that easy cases should be flagged as soon as possible; this property was confirmed by the observation that most events ( ≈ 79%) were detected within 10–20 ms, while at the same time retaining a very high detection rate overall cases ( >99 %).
    DSpace URI
    http://hdl.handle.net/11073/21632
    External URI
    https://doi.org/10.1109/TII.2021.3065015
    Collections
    • Department of Electrical Engineering

    Browse

    All of DSpaceCommunities & CollectionsBy Issue DateAuthorsTitlesSubjectsCollege/DeptArchive ReferenceSeriesThis CollectionBy Issue DateAuthorsTitlesSubjectsCollege/DeptArchive ReferenceSeries

    My Account

    LoginRegister

    Statistics

    View Usage Statistics

    DSpace software copyright © 2002-2016  DuraSpace
    Submission Policies | Terms of Use | Takedown Policy | Privacy Policy | About Us | Contact Us | Send Feedback

    Return to AUS
    Theme by 
    Atmire NV